JYM-3B型便携式三相电能表检定装置英文版的详细介绍
本产品由上海徐吉电气有限公司精心推荐:
产品特性:
All electrical parameters are regarded as standards of the loop output signal, high precision standards and standard source integration design, covering all the functions of the standard source and can output high precision pure sine wave voltage, current, phase, frequency, power, power factor, etc. of electrical parameters signal, built-in high precision standard electric energy meter;
Can be used to test a variety of single (three) phase electronic, mechanical energy meter, multi-function electric energy meter, multi rate watt hour meter, all kinds of electric energy acquisition module, the use of electric collection terminal and other measurement terminal products.
Electric energy cumulative, go test, black label, starting and creeping test range of standard features, can be used to verify the absence of pulse output electric energy meter or meter.
Can arbitrarily set or set required voltage, current, frequency, phase and amplitude value and the flexibility to choose the parameter test and arbitrary regulation set by the magnitude of the, and 2-51 high precision harmonic output, convenient for harmonic test.
The instrument has the function of limiting current protection, power amplifier protection, voltage short circuit protection, current circuit protection, power amplifier thermal protection, etc., can prevent the instrument from all kinds of operation or abnormal situation caused by fault.
The instrument can store 200 sets of electrical energy meter test data, through the RS232 interface and the computer management software can be easily connected with the computer to achieve inligent operation.
产品参数:
AC voltage output: adjust the fineness: 0.01%RG; resolution: 6 effective number
Accuracy: it is better than 0.05%RG; the stability is better than 0.01%RG/1min
Distortion: better than 0.3% (non capacitive load)
Output power: 20VA
File settings: 57.7V, 100 V, 220V, 380V, internal automatic shift switch;
AC current output: adjust the fineness: 0.01%RG; resolution: 6 effective number
Accuracy: the stability is better than 0.05%RG; the stability is better than 0.01% /1min RG
Distortion: better than 0.3%; output power: 20VA.
File settings: 0.2A, 1A, 5A, 20A, 60A (100A), automatic shift switch;
Power output: accuracy: better than 0.05%RG; stability: better than 0.01%/1min. Resolution: 6 bit active power, reactive power, apparent power
Device accuracy: 0.1; 0.05.
Power factor: adjustment range: -1 ~ 0 ~ +1; resolution: 0.00001; accuracy: 0.0005.
Phase adjustment range: 0 to 359.99 degrees, resolution: 0.001 degree accuracy: 0.02
Frequency adjustment range: 45Hz ~ 70Hz resolution: 0.001Hz
Harmonics can be accuray output from 2 to 51 times of harmonic; harmonic accuracy: a grade
Device pulse constant: 24000000 x 5/In
Power supply: single phase 220V 50/60Hz, AC.
Specification; 500*600*178mm; weight: 27Kg.